best live chat
  Order Online or Call Toll-Free 1-800-899-0553  
Log-in/Create Account
 
 $
Search
 
Quick Deliveries of High Quality Valves and Flow Meters
We Make Valve Automation Easy
We Make Valve Automation Easy

R Series 12/24 VDC Wiring Instructions

Assured Automation: your source for Manual and Automated Valves & Flow Meters.

This is the R Series 12/24 VDC Wiring Instructions

The R Series is a reversing motor actuator with end of limit travel switches to stop the motor in either direction.

Safety First: Make sure all power is off. A wiring diagram can be found on our website, or if needed, on the inside cover of the unit.

To access the terminal strip, remove the four screws from the cover and lift off the base. To open or drive the actuator in the counter-clockwise dirction, apply Positive DC Voltage on Terminal One and Negative on Terminal Three. The actuator will turn counter-clockwise until it reaches the internal limit switch and shuts off.

To close, or drive the actuator in the clockwise direction, Apply Negative DC Voltage on Terminal One and Positive on Terminal Four. The actuator will turn clockwise until it reaches the internal limit switch and shuts off.

Auxiliary feedback limit switches may be ordered but are not in the basic unit. Contact sales for additional information.

To engage the manual override, disconnect power, remove the indicator, place a wrench on the stem, press down on the stem to disengage the gears, and slowly turn to the desired position.

Thank you for viewing.
From your friends at Assured Automation
assuredautomation.com
For any other questions contact us online or call toll free at
1-800-899-0553.

Request Automated Valves Process Control

Posted On:

Posted By: