best live chat
  Order Online or Call Toll-Free 1-800-899-0553  
Log-in/Create Account
 
 $
Search
 
Quick Deliveries of High Quality Valves and Flow Meters
We Make Valve Automation Easy
We Make Valve Automation Easy

K Series 120V Electric Actuator-Wiring Instructions

Assured Automation: your source for Manual and Automated Valves & Flow Meters.

This is the wiring instructions for the K Series 120V electric actuator

The K Series is a reversing motor actuator with end of limit travel switches to stop the motor in either direction.

A wiring diagram can be found on our website or if needed on the inside of the actuator cover.

Safety First: Make sure all power is off.

To access the terminal strip remove the 4 screws from the cover.To open or drive the actuator in the counter clockwise direction, apply power to terminal 1 and terminal 2. The actuator will turn counterclockwise until it reaches the internal limit switch and shuts off.

To close or drive the actuator in the clockwise direction, apply power to terminal 1 and Terminal 3. The actuator will turn clockwise until it reaches the internal limit switch and shuts off.

Dry contact limit switches are available for control room feedback. Apply common power to terminal 4. When the actuator reaches the full open position, switch contact is made and feedback is available on terminal 5. When the actuator reaches the full closed position, switch contact is made and feedback is available on terminal 6.

To engage the manual override, disconnect power, remove the black override connection

cap. Remove the crank handle, insert crank handle into override fitting and slowly turn to the desired position.

Assured Automation: Your Source for Manual & Automated Valves and Flow Meters.

Thank you for viewing.
From your friends at Assured Automation
assuredautomation.com

For any other questions contact us online or call toll free at
1-800-899-0553.

Request Automated Valves Process Control

Posted On:

Posted By: